• Extends Fire Detection Control Panels
BC06-1 and BC06-2 by further 2
conventional detector zones
• Individual setting of detector zone
function
• Differentiation between the activation
of automatic detectors and manual
call points on the same detector line
• Lines monitored for wire breakage,
short circuit, and short to earth
Description
With the Zone Extension Board ZEB2-1 a Fire Detection Alarms from manual call points and from automatic de-
Control Panel BC06-1 or BC06-2 can be extended from tectors that are connected together to a detector line
four to six detector zones. In the event of an alarm, the can be differentiated and thus evaluated differently by
fire detection control panel indicates the activation of the fire detection control panel, by means of an optional
the detector zone via LED. Depending on the detector coding module.
type, each of the two detector lines can be individually Each input of the zone extension board is protected
parameterised as detector zone for fire alarms or as against overvoltage and thus provides high system sta-
detector zone for fault messages.
bility.
Specifications
Current consumption at 24V
typ. 14mA (line termination 5.6kΩ, without detectors)
typ. 7mA (line termination 47µF, without detectors)
Line voltage
typ. 20V (line termination 5.6kΩ)
typ. 23V (line termination 47µF)
Line current
typ. 3.7mA (line termination 5.6kΩ)
typ. 0mA (line termination 47µF)
Line termination
Line resistance
Ambient temperature
Dimensions L × W × H
Weight
5.6kΩ or 47µF
max. 50Ω per core
-5°C to +50°C
103 × 58 × 15 (mm)
34g
Order number
210210
Order name
Zone Extension Board ZEB2-1
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
ZEB2-1_DBL_LST_EN_0826.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
|