Lightolier Power Supply L1PH Series User Manual

L1PH Series Uninterruptible Power Supplies L1PH  
Page 1 of 2  
14.0 kVA Single Phase UPS System  
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.  
33.0”  
83.8 cm  
34.0”  
86.4 cm  
30.0”  
76.2 cm  
33.0”  
83.8 cm  
Battery  
Cabinet  
70.0”  
177.8 cm  
Electronics  
Cabinet  
43.5”  
110.5 cm  
How to Specify:  
SERIES  
INPUT  
VOLTAGE  
SYSTEM  
TYPE  
BASE  
SIZE  
BATTERY  
TYPE  
OUTPUT  
VOLTAGE  
OUTPUT  
CKT BRKRS  
# ON 2ND  
VOLTAGE  
NORMALLY  
OFF LOAD  
# OF  
NOL  
NOL  
VOLTAGE  
1
14.0 = 14.0 kVa S = Sealed  
1 = 120 V  
Y = Hardwire  
A = 1 0CB  
B = 2 0CB  
C = 3 0CB  
0
1
2
3
4
A = No  
B = Yes  
C = Yes w/ Time Terminal  
0 = No NOL  
Y = Hardwire  
X = None  
A = 1st  
B = 2nd  
I = ETL Listed  
to UL 924 for  
Emergency  
Lighting  
2 = 208 V  
3 = 240 V  
4 = 277 V  
Z = Special  
Voltage  
L1PH = Single  
Phase  
Uninterruptible  
Power  
Supplies  
Lead Calcium 2 = 208 V  
3 = 240 V  
4 = 277 V  
5 = 120/208 V D = 4 0CB  
6 = 120/240 V E = 5 0CB  
Delay Timer  
1 = 1  
2 = 2  
3 = 3  
Applications  
5
(Consult  
7 = 120/277 V F = 6 0CB  
6
7
8
9
4 = 4  
5 = 5  
6 = 6  
7 = 7  
Factory)  
Z = Special  
Voltage  
(Consult  
G = 7 0CB  
H = 8 0CB  
J = 9 0CB  
NOTE: Input circuit  
breaker not available.  
Input switch is  
Factory)  
K = 10 0CB  
L = 11 0CB  
M = 12 0CB  
N = OCBA1  
P = OCBA2  
R = OCBA3  
S = OCBA4  
T = OCBA5  
U = OCBA6  
V = OCBA7  
W = OCBA8  
X = OCBA9  
10  
11  
8 = 8  
9 = 9  
10 = 10  
11 = 11  
12 = 12  
standard.  
Overall Characteristics  
Electrical  
86% throughput efficiency  
Sine Wave Output  
Operating temperature range 32°F (0°C) to 104°F (40°C)  
Internal maintenance by-pass is standard  
Main load disconnect switch standard  
Double conversion, no interruption  
Standard backup time of 90 minutes, other run times optional  
Output circuit breakers and normally-off loads optional  
Completely solid-state Pulse Width Modulation (PWM) inverter  
16-bit microprocessor control  
Input power factor correction maintains power factor at 0.99  
Transient response 5%; Recovery time, 10 mS (100% load step)  
3:1 crest factor capability  
Inverter output distortion 2.5% THD (at unity power factor)  
Output voltage regulation ±6% of nominal at full load  
Frequency within ±0.05% of nominal  
Housing  
Free standing, NEMA 1 enclosure  
Acid resistant powder coat finish  
Multiple conduit entries  
Inverter efficiency 84%  
Load power factor capability is 0.5 leading to 0.5 lagging  
(Continued on page 2)  
Metering/Controls  
Standard  
Alpha-numeric front panel display with 14 metered measurements and  
53 messages/alarms  
Normal, caution and alarm indicating LEDs  
Audible failure alarms with silence switch  
Dry contact for remote failure alarm  
“D” type 9-pin computer interface connector (see pin config. on back)  
Programmable battery monitor with alarm  
Optional  
Diagnostics software for remote computer (PC) monitoring and control  
Stand-alone remote display mimics all measurements, indications and  
alarms shown on the front panel display  
Lightolier a Genlyte Thomas Company  
Additional RS-232 input/output port for remote monitoring and system  
control  
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710  
We reserve the right to change details of design, materials and finish.  
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504  
 

KTI Networks TV Converter Box KCD 300 User Manual
Kyocera Cell Phone DURAMAX BY KYOCERA User Manual
LevelOne Printer FPS 2112 User Manual
LifeWise Heart Rate Monitor 63 609 User Manual
Linksys Network Card DSSXFXSC User Manual
Logitech Computer Keyboard K300 User Manual
Makita Sander BO5010 User Manual
Makita Trimmer RBC2500 User Manual
Matrox Electronic Systems Computer Hardware Matrox RTX2 User Manual
Microsmith Computer Hardware EXPX6 User Manual