Lux Products Electric Heater LV1 User Manual

Complete, Easy To Read  
Installation and Operating Instructions  
MECHANICAL LINE VOLTAGE THERMOSTATS  
52013  
70  
70  
70  
60  
LO  
60  
50  
OFF  
80  
90  
80  
90  
80  
90  
60  
50  
LO  
50  
LUX  
LUX  
LUX  
LV1  
LV2  
LV3  
SINGLE POLE: Heating Only  
DOUBLE POLE: Heating Only  
SINGLE POLE: Cooling Only  
ELECTRICAL RATINGS:  
ELECTRICAL RATINGS:  
ELECTRICAL RATINGS:  
22 AMPS @ 125 VAC (2600 W)  
22 AMPS @ 250/277 VAC (5000 W)  
0.75 HP @ 125 VAC  
22 AMPS @ 125 VAC (2600 W)  
22 AMPS @ 250/277 VAC (5000 W)  
0.75 HP @ 125 VAC  
22 AMPS @ 125 VAC (2600 W)  
22 AMPS @ 250/277 VAC (5000 W)  
0.75 HP @ 125 VAC  
1.50 HP @ 250/277 VAC  
1.50 HP @ 250/277 VAC  
1.50 HP @ 250/277 VAC  
UL LISTED  
SETTING RANGE:  
50°-90°F (10°-32°C)  
UL LISTED  
SETTING RANGE:  
50°-90°F (10°-32°C)  
UL LISTED  
SETTING RANGE:  
50°-90°F (10°-32°C)  
LINE 1  
LINE  
LINE  
GROUND  
WIRE  
GROUND  
WIRE  
GROUND  
WIRE  
LINE 2  
LOAD 1  
LOAD  
LOAD  
LOAD 2  
LINE Voltage  
LINE Voltage  
LINE Voltage  
Line 1  
Line 2  
Line 1  
Line 1  
• Both poles are  
only broken when  
the dial is in the  
OFF position  
THERMOSTAT  
THERMOSTAT  
THERMOSTAT  
Load 1  
Load 2  
Load 1  
Load 1  
HEATING  
LOAD  
COOLING  
LOAD  
HEATING  
LOAD  
WARNING  
All three of the thermostat models shown above control line voltage (125/250 VAC) directly. Do not attempt to install these unless you are completely familiar  
with house wiring. If proper precautions are not followed, a risk of electric shock may exist, possibly causing severe injury or death. Disconnect power supply  
prior to removing existing thermostat or installing this one. Do not connect to voltages different than the ratings listed above.  
NOTE: The LV2 Double Pole heating only model may also be used in Single Pole applications, however only the LINE 1 and LOAD 1 terminals must be  
used. Only the LINE 1 and LOAD 1 terminals are switched during normal temperature cycling.  
All wiring performed must comply with applicable codes and ordinances to your local area.  
LOCATION:  
The thermostat should be mounted in a standard 2 inch X 3 Inch Electrical Outlet Box. For Ease of installation, use a “deep” style box to assist in allowing room for  
the excess wires. A mounting location should be chosen where it will be constantly exposed to the average room temperature. The thermostat should also be located  
away from the following: concealed hot or cold water pipes, air ducts, hallway drafts, fireplaces, or stairways, to be able to sense temperature and control your heating  
or cooling equipment properly. For the heating only models, avoid positioning this thermostat in a location which is directly above any baseboard heating components,  
as this will cause erratic temperature control.  
INSTALLATION:  
[1] Disconnect the supply power before removing your old thermostat (if applicable) and keep it off until after you have completed installing this thermostat. Double  
check that the thermostat is rated for the voltage and amperage to be switched. [2] If replacing an old thermostat, remove it carefully to avoid damaging the wires or  
their insulation. Check the existing wire insulation for cracks, nicks, or fraying and apply certified electrical tape where necessary to achieve adequate insulation, or  
replace the wires in an approved fashion. [3] For all three heating or cooling models, turn the dial fully counter-clockwise prior to installing. [4] Use the diagrams  
shown above as a guide to ensure a proper connection between your voltage supply and your heating or cooling components, using the appropriate LINE and LOAD  
designations. [5] Attach the connection wires using appropriately sized solderless wire connectors (provided). Be sure that ALL wire connections are securely  
tightened. [6] Ensure that the thermostat is appropriately connected to the ground wire at the grounding screw on the rear of the thermostat housing. [7] Carefully  
bend all of the solid conductors and push the excess wire length to the rear of the electrical box to allow enough room for the rear portion of the thermostat to be  
recessed into the box. Be sure that no portions of the exposed ground wire are allowed to accidentally come in contact with the LINE or LOAD terminals on the rear of  
the thermostat. [8] Carefully push the thermostat all the way into the box opening, and mount the thermostat to the box using appropriately sized mounting screws.  
Ensure that the mounting screws will not project too far into the box and come in contact with any of the wires causing a short circuit. [9] Once complete, turn the  
power back on to your heating or cooling equipment and turn dial to the desired temperature setting.  
NOTE:  
Model LV2 is intended for use on 250 or 277 volt heating systems where local codes require that a double line disconnect thermostat be used. On the LV2 model,  
only LINE 1 is broken during normal temperature cycling of this thermostat. Both LINE 1 and LINE 2 are broken when the dial is turned to the OFF position.  
TECHNICAL ASSISTANCE  
If you have any problems installing or using this thermostat, please carefully and thoroughly review this instruction manual. If you require assistance, please contact our  
Technical Assistance Department at 856-234-8803 during regular business hours between 8:00AM and 4:30PM Eastern Standard Time, Monday through Friday. You  
questions, and also permits you to email your questions to our technical support staff at your convenience.  
WARRANTY  
Limited Warranty: If this unit fails because of defects in materials or workmanship within three years of date of original purchase, LUX Products Corporation will, at its  
option, repair or replace it. This warranty does not cover damage by accident, misuse, or failure to follow installation instructions. Implied warranties are limited in  
duration to three years from date of original purchase. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not  
apply to you. Please return malfunctioning or defective units to the participating retailer from which purchase was made, along with proof of purchase. Please refer to  
"TECHNICAL ASSISTANCE" before returning thermostat. Purchaser assumes all risks and liability for incidental and consequential damage resulting from installation  
and use of this unit. Some states do not allow the exclusion of incidental or consequential damages, so the above exclusion may not apply to you. This warranty gives  
you specific legal rights and you may also have other rights which vary from state to state. Applicable in the U.S.A. only.  
©
COPYRIGHT 2006 LUX PRODUCTS CORPORATION. ALL RIGHTS RESERVED  
 

Kustom Musical Instrument Amplifier KG112FX User Manual
Leica Microscope Magnifier Leica EZ5 User Manual
LevelOne Door WBR 3460 User Manual
LG Electronics Car Satellite TV System 32LX570H User Manual
Life Fitness Home Gym Ab Back Machine User Manual
Linksys Network Card EG0801SK User Manual
Mackie DJ Equipment U420D User Manual
Magnavox DVD VCR Combo MDV 530 VR User Manual
Maytag Washer Dryer MDE2400AYW User Manual
Microsoft Computer Accessories 22809175 User Manual